products

CoolFlow NTP Physical Properties

Density:

1.02 - 1.15 g/cm³ depending on inhibitors

pH:

7.5 - 10.5 depending on inhibitors.

Boiling Point:

>100°C

Characteristics:

a clear, slightly viscous liquid. It is mildly sweet to the taste and has a non-pungent but characteristic aroma.

Available in:

5, 10, 15, 20, 25, 205 & 1000 litre containers and bulk tankers.

Datasheets

For a quote or assistance

Tel: +44 (0) 1792 586800
Email: info@hydratech.co.uk

Non-Toxic Secondary Refrigerant Antifreeze, based on Propylene Glycol and BS6580 & ASTM D1384 proven Corrosion, Scale and Biological Inhibitors.

CoolFlow NTP has been especially formulated for use as a Non-Toxic Secondary Refrigerant Antifreeze for use in Process Cooling, Refrigeration and Air Conditioning Systems.


Antifreeze AntiFreeze

CoolFlow NTP is miscible with water in all proportions and can protect RAC systems down to -50°C depending on concentration. CoolFlow NTP exhibits super-cooling characteristics and mixtures containing in excess of 50% by volume do not freeze solid, alleviating any concern over possible expansion and burst damage.

non toxic Non-Toxic

CoolFlow NTP has an LD50 toxicity rating (Oral Rat) of ≥15,000 mg/kg of body weight (bw) = “Relatively Harmless” as confirmed by the Hodge & Sterner Scale.

Corrosion control Corrosion Control

CoolFlow NTP contains synergistic corrosion inhibitors to protect metals commonly found in such systems. It has been tested in accordance with BS5117 and found to meet BS6580 and ASTM D1384 corrosion standards.

CoolFlow NTP also contains scale and biological inhibitors to help prevent fouling – thus promoting long operational life and high thermal efficiency.

Biodegradable Biodegradable

CoolFlow NTP mixtures are readily biodegradable (90% over ten days) and will not remain in the environment or bio-accumulate.

Quality Assured Quality Assured

All Hydratech products are manufactured in accordance with certified ISO9001-2008 procedures

Application

As per BSRIA guide BG 29/2012 all pipe-work systems should be clean and free from biological contamination and debris prior to commissioning.

To minimise corrosion air ingress should be minimized. A pressurised system is best. 

├»┬╗┬┐Determine the total system volume and add CoolFlow NTP to the system according to the minimum operating temperature required (see table). The minimum dose of CoolFlow NTP should not be less than 25% of the system volume and the maximum does not normally exceed 60%. We recommend the use of deionised, distilled or UltraPure™ water for this dilution. Avoid water containing high levels of calcium salts or Chlorides [Cl-].

Health & Safety: Please refer to the associated Safety Data Sheet. Available via Login or upon request.

Shelf Life: 3 years when stored in sealed containers out of direct sunlight.

Available in: 5, 10, 15, 20, 25, 205 & 1000 litre containers and bulk tankers.

CoolFlow NTP can also be supplied as a Ready-To-Use solution.

Mixing Guide

Frost Protection °C v/v of CoolFlow NTP Refractive Index
-10 25% 1.356
-15 33% 1.364
-20 39% 1.370
-25 44% 1.373
-30 48% 1.380
-35 52.5% 1.383

When measuring the percentage of CoolFlow NTP in the system use a refractometer

back to all CoolFlow fluids